联系我们

湖北久歌电气有限公司(中英文).png

电话:86 717 4209228

          86 717 4209218

传真:86 717 4209218

邮箱:info@jucro.com

地址:中国 湖北 枝江市 仙女四路


真空断路器
当前位置: 首页 > 产品 > 真空断路器
HVD7

HVD7 vacuum circuit breaker.png

1. Introduction

HVD7-40.5 outdoor HV AC vacuum circuit breaker has many visual advantages like reasonable design, fashionable appearance, high safety and reliability, simple maintenance, long electric life. It is the ideal upgraded products of 35KV outdoor oil circuit breakers.

HVD7-40.5 vacuum circuit breaker is applicable for three-phase power system of AC 50HZ.It is used to make and break the load current ,overload current and short-circuit current.

HVD7-40.5户外交流高压真空断路器(ZW7-40.5),具有设计合理、外形新颖、安全可靠、维护简便、电寿命长等优点。是35KV户外多油断路器更新换代的理想产品。

    HVD7型真空断路器用于交流50Hz的三相电力系统中,作为分合负荷电流、过载电流及短路电流之用。

 

 

2. Applicable environment

2.1The ambient temperature should be -30℃~ +40℃(-40℃ in the frosty area);

2.2Altitude should not exceed 2000m(over 2000m is plateau type);

2.3The wind pressure should not exceed 700Pa(equal to wind speed 34m/s);

2.4Air pollution degree: Ⅲ,that of antifouling type:Ⅵ;

2.5The installation site should be free from the fire, explosion, chemical corrosion and serious vibration.

2.使用环境

2.1周围空气温度不高于+40℃,不低于-30℃(严寒地区-40℃);

2.2海拔不超过2000米(2000米以上为高原型);

2.3风压不超过700Pa(相当于风速34m/s);

2.4空气污秽程度III级,防污型Ⅳ级;

2.5无火灾、爆炸危险、化学腐蚀及剧烈振动的场所。

 

 

 

1. Main technical parameters

 

No.

Item项目

Unit单位

Date参数

1

Rated voltage额定电压

KV

40.5

2

Rated insulation

Level

额定绝缘水平

1min power frequency

withstand voltage

1分钟工频耐压

Dry test

KV

95

Wet test

80

Lightning impulse withstand voltagepeak value

雷电冲击耐受电压(峰值)

185

3

Rated current额定电流

A

1600

2000

4

Rated short-circuit breaking current

额定短路开断电流

KA

20

25

31.5

5

Rated short-circuit making currentpeak

额定短路关合电流(峰值)

KA

50

63

80

6

Rated operating sequence

额定操作顺序


O-0.3s-CO-180s-CO

7

Rated short-time withstand current

额定短时耐受电流

KA

20

25

31.5

8

Rated peak withstand current

额定峰值耐受电流

KA

50

63

80

9

Rated short-circuit duration

额定短路持续时间

S

4

10

Rated control voltage

额定控制电压

V

AC220,110;DC220,110

11

Rated short-circuit breaking current break times

额定短路开断电流开断次数

Times

20

12

Full-break time

全开断时间

ms

≤80

13

Mechanical life

机械寿命

Times

10000

 


  • 上一条信息:JN15-12KV
  • 下一条信息:?????????!